PVC 4 Core Motor Lead Cable: AWG Sizes : ( With Divisible Earth Core)

Type TW, TWU, THW UL listed Submersible Pump Cable for borehole pumps with 3 and 4 conductors with or without Ground. Sizes range from 14 AWG to 350 MCM with PVC or TPE jacket.
These cables are manufactured from pure virgin copper wires and a specially formulated PVC & TPE compound to meet most stringent requirements of UL 83.
The cables are listed as UL and ULc and are suitable for operation upto -400 C temperature

  • Conductor:High purity electrolytic grade bright annealed flexible bunched bare, copper conductor according to international standards like IS 8130, BS 6360, IEC 228 & VDE 0295.
  • Insulation:Specially developed dielectric grade PVC Compound impervious to water, oils, grease etc.
  • Sheath:High abrasion resistant tough & flexible PVC Compound.
  • IS 694, BS 6500, IEC 60227, CEI 20-20, VDE 0281, SABS 1574, AS 3191, AS/NZS 5000.1, HD 21.1, NF C 32-201, French Standard 32-102-16
  • 450/ 750 V, 600/ 1000 V, 650/1100 V
  • 3000 V
  • -150C to 700 C
  • A07VVH6-F, H07VVH6-F
Core colors (For Asian, African Markets) (For European Markets)
4 core  Red ,Yellow, Blue, Green  Black, Blue, Brown, Green
Sheath color: Blue Blue
 

PVC 4 Core Flat Cables With Divisible Earth Core

Number of cores x
cross-section no. x sq mm
Outer dimensions
mm x mm
Max. conductor resistance at 200C
ohm /km
Current carrying capacity at 400C
amps.
4G x 1.0 15.0 x 4.6 18.1 11
4G x 1.5 16.4 x 5.0 12.1 14
4G x 2.5 19.4 x 6.0 7.41 18
4G X 4 22.7 x 6.7 4.95 26
4G X 6 25.6 x 7.7 3.3 31
4G X 10 32.2 x 9.4 19.1 42
4G X 16 37.7 x 10.8 1.21 57
4G X 25 46.0 x 13.1 0.78 72
4G X 35 51.0 x 14.4 0.554 90


Note:
Insulation thickness, Sheath thickness and overall dimensions are nominal values. The number of wires is approximate and strand diameter is nominal; they shall be such as to satisfy the requirements of conductor resistance as per IS 8130/1984, BS-6360, IEC-60228 & VDE-0295.